Cooling Method: | Cross Flow |
---|---|
Ventilation Mode: | Natural Ventilation |
Material: | PVC |
Air Contact Form: | Wet |
Air Contact Way: | Open |
Tower Shape: | Square |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
Model--RYH | PP |
Max.length | 1080 mm |
Width | 620 mm |
Normal size | 620 x 900 mm, 620 x 1000 mm, 620 x 1080 mm |
Continuous operation temperature |
85ºC |
Max. application temp. (short term) |
90ºC |
Color | White ( customizable) |
Corrugation height | 18 mm |
Installation method | Hung |
No. | Item | symbol | unit | index | test method | |
1 | density | ρ | g/cm3 | ≤1.55 | GB/T 1033 1-2008 | |
2 | tensile strength | lengthways | σt | MPa | ≥42.0 | GB/T 13022-1991 |
crosswise | ≥38.0 | |||||
3 | tear strength | lengthways | σtr | kN/m | ≥150 | GB/T 1130-91 |
crosswise | ≥160 | |||||
4 | Folded in half Coldness Resistance Temperature |
ordinary type | tb | ºC | ≤-8 | DL/T 742-2001 |
Frigostabile type | ≤-18 | |||||
5 | oxygen index | OI | -- | ≥30 | GB/T 2406 1-2008 |