Customization: | Available |
---|---|
Cooling Method: | Cooling Tower |
Certification: | ISO, CE |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Key Features of the Product
· Perfectly tailored for cross flow type cooling towers, ensuring optimal performance.
· Options for both hanging or adhesive attachment available for versatile installation.
· Features highly efficient cellular drift eliminators, seamlessly integrated within the fill sheet for maximum efficiency.
· The fill sheets are expertly crafted with integrally molded louvers to prevent water loss and guarantee perfect air distribution, even across varying airflow conditions.
· Made from thermoformed PVC, boasting a flame spread rating and designed to be self-extinguishing for added safety.
Detailed Visuals & Imagery
Properties
For customized MBH film fill that caters to your precise specifications—be it length, width, material, or thickness—reach out to us with your detailed requirements. We at Newin are dedicated to addressing all customer needs, ensuring you receive the most accurate solution and competitive offer. Additionally, upon request, we provide fill media that feature flame-retardant or anti-bacterial properties, tailored to enhance your cooling tower's efficiency and safety.
Module Length (Max) | mm | 4000 | ||
Module Width | mm | 800/900/1000/1100/1200 | ||
Module Depth | mm | - | ||
Flute Height | mm | 19 | ||
Flute Corrugation Angle | degrees | - | ||
Surface Area | m2/m3 | 150 | ||
Sheet Thickness - Before Forming | mm | 0.32 | ||
Sheet Thickness - After Forming | mm | 0.28 | ||
Max. application temp. (short time) - PVC | °C | 60 | ||
Max.operating temp. (short time) - High temp. | °C | 80 | ||
Customized size and thickness available for special request. Contact Newin for details. |
Application & Usage
The Newin MBH Film Fill is meticulously crafted for optimal performance in cross flow cooling towers. Rigorously tested under SGS standards, adhering to ASTM guidelines, this high-quality infill is designed to maximize the efficiency of your cooling tower operations. Simply provide us with your tower model or dimensions, and we'll meticulously calculate the number of sheets you need for seamless replacement.
Property | Test Method | Values | ||
Specific Gravity | ASTM D792-13 Method B |
1.426g/cm3 | ||
Oxygen Index | ASTM D2863-13 | 34.50% | ||
Tear Strength | ASTM D1004-13 | X direction | 111 N | |
Y direction | 121 N | |||
Tensible Test | ASTM D 882-12 | Tensile Strength | X direction | 51.1 MPa |
Y direction | 45.3 Mpa | |||
Elongation at Break |
X direction | 87% | ||
Y direction | 56% | |||
Values shown above based on SGS Test No.: GZIN1708039662PS by Newin | ||||
Statements and methods presented are based upon the best available information and practices known to Newin. Conditions of use may vary and are beyond control, the user should undertake sufficient tests to determine the suitability for any intended use of the material. |
Discover Other Exciting Opportunities: Explore an Array of Innovative Solutions Awaiting You
NEWIN FACTORY
Embark on an awe-inspiring journey to discover our cutting-edge manufacturing base, strategically nestled in the bustling industrial hub of Huizhou, Guangdong. Covering an extensive 10,000 square meters, this facility stands as a luminous beacon of innovation, excellence, and pioneering technological advancements in the industry.
ISO CERTIFICATION
We proudly highlight our unwavering dedication to supreme quality and environmental leadership, underscored by our prestigious ISO certifications: ISO9001:2015 for Quality Management and ISO14001:2015 for Environmental Management. These accolades set the benchmark for industry excellence.
WORKSHOPS
State-of-the-Art Welding Workshop
Leading-Edge Filler Thermoforming Workshop
High-Precision Sheet Metal Processing Workshop
Comprehensive Cooling Tower Assembly Workshop
Open type cooling towers shipment: Experience a new standard of security and precision with our expertly organized shipping service for open-type cooling towers. Each tower is meticulously enveloped with top-tier materials and cutting-edge packing techniques, ensuring their pristine arrival at your doorstep. Our steadfast commitment to safeguarding your investment means comprehensive protection against any potential transit challenges. Benefit from our seamless logistics and on-time delivery, thoughtfully designed to initiate your cooling solutions without any delay.