Adiabatic Cooler NWFL-VA Series
NWFL-VA series is the V type dry air cooler designed with Adiabatic Cooling System. Efficient cooling throughout the year, free cooling solution suitable for data center and other facilities, and water consumption is greatly reduced compared with evaporative cooling.
Features
· V type design and adiabatic cooling system,
High cooling efficiency with low water consumption.
· Optimal efficient components, like EC motor
Maximum system efficiency and energy saving.
· Large redundancy available,
Eliminating thermal performance loss.
· High reliability and Ease maintenance.
Working Principle
When NWFL-VA adiabatic cooler is in operation:
Cold water will flows from the top of the cooler and envenly through the evaporative cooling pads. The cool dry air will be drawn into by EC axial fan over the pads and precooled. This adiabatic precooling of the air has larger cooling capacity for cooling the warm process fluid.
Series |
Type |
Capacity |
1. Fan Drive System |
2. Heat Exchange System |
3. Adiabatic Pre-cooler |
NWFL-VA |
V |
Range |
EC axial fans |
Finned coil |
Evaporative cooling pads |
Maximum thermal performance |
300~1680kw |
Intelligent frequency conversion,
more energy saving |
Maximum heat transfer surface |
Precooling the ambient air temperature,
improving higer cooling efficency |
*4.The wake up is on the top of the pads can ensure the cool dry air in adiabatic precooling process when the pump is not running. |
*5. Recirculation system is designed for further reduce the total water consumption. |
Adiabatic cooling
system |
Exceeding 90% annual water saving compared to normal cooling tower |
Application |
Small to medium industries & HVAC;
The places with limited water consumption;
High temperature industrial cooling process etc. |
Parameter
Model |
Configuration Mode |
Flow |
Cooling Capacity |
Dimension (mm) |
Nos of Fins |
Fan Diameter |
Power |
F/V |
m3/h |
kw |
L |
W |
T |
nos |
mm |
kw |
NWFL-300VA |
V |
52 |
300 |
4000 |
1290 |
198 |
2 |
EC900 |
7.6 |
NWFL-600VA |
V |
104 |
600 |
4000 |
1290 |
198 |
4 |
EC900 |
15.3 |
NWFL-520VA |
V |
90 |
520 |
4500 |
1786 |
198 |
2 |
EC800 |
12.6 |
NWFL-1040VA |
V |
180 |
1040 |
4500 |
1786 |
198 |
4 |
EC800 |
25.3 |
NWFL-600VA |
V |
105 |
600 |
4000 |
2280 |
198 |
2 |
EC900 |
15.3 |
NWFL-1200VA |
V |
210 |
1200 |
4000 |
2280 |
198 |
4 |
EC900 |
30.6 |
NWFL-840VA |
V |
144 |
840 |
5500 |
2777 |
198 |
2 |
EC900 |
19.1 |
NWFL-1680VA |
V |
288 |
1680 |
5500 |
2777 |
198 |
4 |
EC900 |
38.2 |
* This table sample only contains the data when issued, please do not use for engineering construction. Please further to confirm with sales and engineer about the detailed data before purchasing.
* If need muti- cells, please consult the manufacturer to provide the solutions. NEWIN reserves the right to change the parameters or dimensions of the table without notice.
Components& Options
· Heavy-duty Construction
The galvanized steel panel with NWN-Armour anti-corrosion coating have excellent resistance and corrosion resistance approaching the characteristics of stainless steel, allows the equipment to work with higher concentration cycles and thereby reduce water consumption. The coating can be easily repaired if damaged.
· V Type Finned Coil Heat Exchanger
The finned coil heat exchanger made with copper tubes and aluminum fins adequately spaced to ensure the best performance in heat exchange. The copper tubes are fixed to the coil headers by brazing and to the finned coil by flaring, to ensure maximum continuity in thermal conduction.
· EC Axial Fan
- EC motor straight-shaft drive, motor protection grade is IP55, insulation grade is F, suitable for long-term operation in hot and humid environments, with smooth operation. The energy efficiency of EC motors can reach IE4 or above.
- The fan bearings adopt tapered roller bearings, which have large load-bearing capacity and long service life, with a rated service life of more than 20,000 hours.
- Through static and dynamic testing during the production process, noise is minimized while meeting the heat exchange performance of the cooler; using PFC to keep harmonics below 35%, the EC fan system can maintain high static efficiency, even at low speeds.
· Adiabatic Pre-cooler
- Evaporative cooling pads are made of cellular materials of impregnated cellulose with different flute and constructed in heavy gauge stainless steel framework. Water distribution from top of the pads for complete wetting.
- Evaporative cooling pads with water circulation pump can help to achieve designed conditions in peak summer.
· Adiabatic Intelligent controls
- EC fans Intelligent frequency conversion to meet different working conditions on site, save more energy.
- Force unit in dry operation in case water usage is prohibited.
· Options
- Increase the coil's resistance ability
- Coil freeze-up safeguard
- Low noise upgrade
- Increase the degree of redundancy If any customized requirements, please contact NEWIN sales representative.
NEWIN Manufacturing Base
NEWIN FACTORY
Manufacturing base Situated In Huizhou, Guangdong. It Covers An Area Of 10,000 Square Meters.
ISO CERTIFICATION
ISO9001:2015 Quality Manergement System Certification ISO14001:2015 Environmental Manergement System Certification
WORKSHOPS
Welding Workshop
Filler Thermoforming Workshop
Sheet Metal Processing Workshop
Cooling Tower Assembly Workshop
TESTING
Independent Testing LAB
NEWIN COOLING TOWERS:
·
NWN/ NWF/ NCFN Closed Type Cooling Tower Series
·
NSH/ NST Open Type Cooling Tower Series
·
NTG Industrial Type Cooing Tower Series
·
NECN/NECH Evaporative condenser
·
NWFL Dry Air Cooler
NEWIN manufactures and stocks all major cooling tower accessories to meet maintenance and replacement needs of almost any size and types of cooling tower. Please contact us to customize the cooling tower accessories you need.
CONTAIN:
· Fan drive system (fan/ fan stack/reducer/motor/shaft etc.)
· Water distribution (nozzles/ drift eliminator etc.)
· Heat exchange(PVC infills/ cooling coil etc.)
· Other accessories (air inlet louver/ valve etc.)
Packaging & Shipping
Open type cooling towers shipment
Closed type cooling towers shipment
Technical Strength& Standards
Certifications