Cooling tower PVC fills for round Type Cooling Tower Infill ,230/250/300/350mm Width
YN counter flow film fill is widely used in counter flow cooling towers, the product is a cellular block after bonding molding, according to the interval size of the tower bracket, cut into different sizes. Easy to installation. High heat exchange efficiency, small wind resistance, no-easy plugged. PVC, PP material are both available. Customers can choose according to cooling media temperature.
Features
- Advanced technology, reasonable design, with good cooling effect.
- Good ventilation, small resistance, strong hydrophilic, large contact area, and good film-forming, easy packing, good heat conductivity, good chemical stability, acid, alkali and organic solvent corrosion, etc.
- The staggered ring material form assembling, packing general is 60 ° Angle, polyvinyl chloride (PVC), polypropylene (PP) two kinds of packing material available.
PROPERTIES
With different request in YN film fill, like length and width, materials or thickness, etc, please inform us your detailed request to get correct solution and offer. Newin could cover all customer requirements. Fill media in flame retardant or anti-bacterial execution are also available on request.
Module Length (Max) |
mm |
by roll |
Module Height |
mm |
230 / 250 / 300 / 350 |
Flute Height |
mm |
18 / 25 |
Flute Corrugation Angle |
degrees |
- |
Sheet Thickness - Before Forming |
mm |
0.3 |
Sheet Thickness - After Forming |
mm |
0.3 |
Max. application temp. (short time) - PVC |
°C |
60 |
Max.operating temp. (short time) - PP |
°C |
95 |
Customized size and thickness available for special request. Contact Newin for details. |
STRUCTURE & INSTALLATION DRAWING
Newin supply structure & installtion drawing advice with jobsite storage advice and quality control report along with shipment to make attention to customers when they receive the materals. OEM or special mold design also available on request.
APPLICATION & USAGE
Newin LXN counter flow film fill is applicable for counter flow cooling towers and other counter flow cooling tower, with SGS test to keep high quality infill to get the high efficiency of the cooling tower. Inform us the tower model or size, we will estimate the Nos of sheets needed for your cooling tower replacing.
APPLICABLE COMMERCIAL STANDARDS
Sheets material is strictly followed below SGS test with ASTM standards. Each property or all properties as below tested by your products are also vailable on request.
Property |
Test Method |
Values |
Specific Gravity |
ASTM D792-13 Method B |
1.426g/cm3 |
Oxygen Index |
ASTM D2863-13 |
34.50% |
Tear Strength |
ASTM D1004-13 |
X direction |
111 N |
Y direction |
121 N |
Tensible Test |
ASTM D 882-12 |
Tensile Strength |
X direction |
51.1 MPa |
Y direction |
45.3 Mpa |
Elongation at Break |
X direction |
87% |
Y direction |
56% |
Values shown above based on SGS Test No.: GZIN1708039662PS by Newin |
Statements and methods presented are based upon the best available information and practices known to Newin. Conditions of use may vary and are beyond control, the user should undertake sufficient tests to determine the suitability for any intended use of the material. |
FILED DATA FOR COUNTER FLOW FILM FILL REPLACEMENT
Fill in below measurements data for your maintenance cooling tower or reparing projects demand quality and reliability, count on Newin, site visit or maintenance service, engineered to fit the cooling tower fills or components.
YN Infill Pictures --- cooling tower counter flow film fill
Packing & Shipment
NEWIN Manufacturing Base
NEWIN FACTORY
Discover the expansive manufacturing base of NEWIN, nestled in the industrial heartland of Huizhou, Guangdong. This state-of-the-art facility spans a sprawling 10,000 square meters, dedicated to excellence in every facet of production.
ISO CERTIFICATION
NEWIN proudly upholds the highest standards with ISO9001:2015 Quality Management System Certification and ISO14001:2015 Environmental Management System Certification, ensuring impeccable quality and sustainable practices.
WORKSHOPS
Welding Workshop
Filler Thermoforming Workshop
Sheet Metal Processing Workshop
Cooling Tower Assembly Workshop
TESTING
Independent Testing LAB
NEWIN COOLING TOWERS:
·
NWN/ NWF/ NCFN Revolutionary Closed Type Cooling Tower Series, engineered for optimal efficiency and performance.
·
NSH/ NST Innovative Open Type Cooling Tower Series, designed for versatility and reliability in diverse applications.
·
NTG Robust Industrial Type Cooling Tower Series, crafted for heavy-duty cooling solutions.
·
NECN/NECH Advanced Evaporative Condenser, for superior thermal management and energy efficiency.
·
NWFL Efficient Dry Air Cooler, offering reliable performance in varied cooling requirements.
At NEWIN, we manufacture and maintain an extensive inventory of essential cooling tower accessories, ready to meet the diverse maintenance and replacement needs for any size or type of cooling tower. Reach out to us for customized solutions tailored to your specific requirements.
CONTAIN:
· Comprehensive Fan Drive System (including fan, fan stack, reducer, motor, shaft, etc.)
· Advanced Water Distribution Components (featuring nozzles, drift eliminator, etc.)
· Superior Heat Exchange Elements (such as PVC infills, cooling coil, etc.)
· Additional Accessories (including air inlet louver, valve, etc.)
Packaging & Shipping
Open Type Cooling Towers Shipment: Ensuring the safe and secure delivery of our remarkable open type cooling towers, we meticulously package each unit to withstand the rigors of transport. Our commitment to excellence extends beyond manufacturing to include reliable shipping solutions, ensuring your equipment arrives in pristine condition.
Closed Type Cooling Towers Shipment: We take immense pride in our thoughtful shipping process for closed type cooling towers. Each unit is packaged with precision and care, guaranteeing that it reaches its destination intact and ready for seamless integration into your operations. Trust in our dedicated approach to deliver not just a product, but a promise of quality.
Technical Strength& Standards
Certifications