200RT FRP Counter Flow Induced Draft Cooling Tower
Model Description
♦ High efficiency, save energy to the largest extent
♦ Fit with various environment changes in different indutries
♦ Matched equipment running normaly
♦ Completely comply with national standards
Components Instruction
CASING AND WATER BASIN
Fiberglass reinforced polyester (FRP) is applied with water-resistance resin and high quality fiberglass mat. With good moisture, high gel,high strength, spray the gel-coat on FRP parts by machine and is thermal formed.
FAN & DRIVING SYSTEM
All cooling tower fans with adjustable pitch blades are applied to being balanced, it operates stably and quietly. Material chosen are A.B.S, aluminum alloy for normal standard, F.R.P or stainless steel material available for option.Small capacity cooling tower adopts direct drive low noise fan. Bigger capacity fan equipped with Belt drive speed reducer or Gear box.
WATER DISTRIBUTION
Using high coefficient rotating sprinkler head made of plastic or aluminum alloy could reduce the pressure of friction loss, and the water can be distributed evenly to achieve the max thermal cooling performance.
FILL PACKING
Used high quality & improved performance PVC with good material, it is high cooling efficiency and anti-corrosive & UL V-0. The surface of infill is corrugated to increase the filling pitch to make sure that infill is clog-free and overcome the problem of water quality. Special material for option if high entering water temperature.
FRAME
The framework is made of hot dip galvanized steel (HDGS), to makes the cooling tower in rust-free, durable and long service life.
Optional Accessories
♦ Noise reduction upgrade ♦ Anti-Freeze heater
♦ Vibration isolator & rubber mat ♦ Stainless steel framework / bolts and nuts (304 / 316)
♦ High-temperature upgrade ♦ Dual-speed Motor & VFD motor /Anti-Freeze heater
Technical data
Item |
Cooling Capacity
(RT) |
Water Flow
(m3/h) |
Dimension (mm) |
Fan |
Air Flow (cmm) |
Water Pressure (Kpa) |
Weight (kg) |
Noise dB(A) |
Model |
Diameter |
Height |
Diameter
(mm) |
Motor (Kw) |
Dry |
Wet |
NRT-8 |
8 |
6.2 |
945 |
1380 |
525 |
0.18 |
70 |
12 |
42 |
180 |
53 |
NRT-10 |
10 |
7.8 |
945 |
1530 |
600 |
0.18 |
85 |
14 |
46 |
190 |
53.5 |
NRT-15 |
15 |
11.7 |
1195 |
1415 |
600 |
0.37 |
140 |
12 |
54 |
290 |
53.5 |
NRT-20 |
20 |
15.6 |
1195 |
1590 |
730 |
0.55 |
160 |
16 |
67 |
300 |
53.5 |
NRT-25 |
25 |
19.5 |
1400 |
1820 |
730 |
0.75 |
200 |
16 |
98 |
500 |
54 |
NRT-30 |
30 |
23.4 |
1650 |
1705 |
730 |
0.75 |
230 |
15 |
116 |
530 |
54 |
NRT-40 |
40 |
31.2 |
1650 |
1775 |
890 |
1.5 |
280 |
16 |
130 |
550 |
54 |
NRT-50 |
50 |
39.2 |
1830 |
1835 |
890 |
1.5 |
330 |
16 |
190 |
975 |
54 |
NRT-60 |
60 |
46.8 |
2145 |
1955 |
1150 |
1.5 |
420 |
17 |
240 |
1250 |
54.5 |
NRT-80 |
80 |
62.6 |
2145 |
2035 |
1150 |
1.5 |
450 |
18 |
260 |
1280 |
55 |
NRT-100 |
100 |
78.1 |
2900 |
2370 |
1410 |
2.2 |
700 |
17 |
500 |
1690 |
55 |
NRT-125 |
125 |
97.5 |
2900 |
2555 |
1410 |
2.2 |
830 |
19 |
540 |
1640 |
56 |
NRT-150 |
150 |
117 |
2900 |
2555 |
1410 |
2.2 |
950 |
22 |
580 |
1680 |
56.5 |
NRT-175 |
175 |
136.8 |
3310 |
3165 |
1750 |
4 |
1150 |
22 |
860 |
1960 |
56.5 |
NRT-200 |
200 |
156.2 |
3310 |
3165 |
1750 |
4 |
1250 |
23 |
880 |
1980 |
57 |
NRT-225 |
225 |
175.5 |
4120 |
3580 |
2100 |
5.5 |
1500 |
24 |
1050 |
2270 |
57 |
NRT-250 |
250 |
195.1 |
4120 |
3580 |
2100 |
5.5 |
1750 |
26 |
1080 |
2800 |
58 |
NRT-300 |
300 |
234 |
4730 |
3680 |
2400 |
7.5 |
2000 |
24 |
1760 |
3930 |
59 |
NRT-350 |
350 |
273.2 |
4730 |
3680 |
2400 |
7.5 |
2200 |
26 |
1800 |
3790 |
60 |
NRT-400 |
400 |
312.1 |
5600 |
3840 |
2745 |
11 |
2400 |
27 |
2840 |
5740 |
61 |
NRT-500 |
500 |
392.4 |
5600 |
3840 |
2745 |
15 |
2600 |
28 |
2900 |
5800 |
61 |
NRT-600 |
600 |
468 |
6600 |
4470 |
3400 |
15 |
3750 |
32 |
3950 |
9350 |
61.5 |
NRT-700 |
700 |
547.2 |
6600 |
4470 |
3400 |
18.5 |
3750 |
33 |
4050 |
9450 |
62 |
NRT-800 |
800 |
626.4 |
7600 |
4720 |
3700 |
22 |
5000 |
32 |
4700 |
11900 |
62.5 |
NRT-1000 |
1000 |
781.2 |
7600 |
4720 |
3700 |
22 |
5400 |
33 |
4900 |
12100 |
63 |
NEWIN Manufacturing Base
Explore the State-of-the-Art NEWIN FACTORY
Our expansive manufacturing base is prominently located in Huizhou, Guangdong, sprawling over a vast 10,000 square meters.
Exemplary ISO CERTIFICATION
We proudly hold the ISO9001:2015 Quality Management System Certification and the ISO14001:2015 Environmental Management System Certification, underscoring our commitment to quality and sustainability.
CUTTING-EDGE WORKSHOPS
Advanced Welding Workshop
Precision Filler Thermoforming Workshop
Innovative Sheet Metal Processing Workshop
Efficient Cooling Tower Assembly Workshop
RIGOROUS TESTING
Comprehensive Independent Testing LAB
NEWIN COOLING TOWERS: A Range to Suit Every Need
·
NWN/ NWF/ NCFN - Our superior Closed Type Cooling Tower Series, engineered for optimal performance.
·
NSH/ NST - Versatile Open Type Cooling Tower Series, designed for maximum efficiency.
·
NTG - Robust Industrial Type Cooling Tower Series, built for durability and high capacity.
·
NECN/NECH - High-performance Evaporative Condenser, offering superior heat exchange solutions.
·
NWFL - Efficient Dry Air Cooler, ensuring reliable and consistent cooling.
NEWIN ensures that all essential cooling tower accessories are available to cater to maintenance and replacement needs, no matter the size or type. Reach out to us for tailored solutions to your cooling tower accessory requirements.
CONTAIN: Essential Components for Superior Functionality
· Comprehensive Fan drive system including fan, fan stack, reducer, motor, shaft, and more.
· Advanced Water distribution components, featuring nozzles and drift eliminator for optimal performance.
· Efficient Heat exchange elements, with PVC infills and cooling coil as standard.
· Additional vital accessories such as air inlet louvers and valves to enhance system efficiency.
Packaging & Shipping
Open Type Cooling Towers Shipment: Experience hassle-free and efficient delivery with our expertly managed logistics tailored for our open type cooling towers. Each shipment adheres to stringent quality checks to ensure your product arrives in impeccable condition, ready for immediate deployment. Trust in our commitment to delivering excellence, every time.
Closed Type Cooling Towers Shipment: With a focus on protection and reliability, our closed type cooling towers are shipped with utmost care. Our comprehensive shipping solutions are designed to safeguard your investment, providing peace of mind with every delivery. Rely on our meticulous attention to detail to ensure your cooling tower arrives safely and punctually, ready to exceed expectations.
Technical Strength& Standards
Certifications